Work item:
|
L.HESS-AIDC
|
|
Subject/title:
|
General Requirements for Hybrid energy storage for AI data centers
|
|
Status:
|
Under study
|
|
Approval process:
|
AAP
|
|
Type of work item:
|
Recommendation
|
|
Version:
|
New
|
|
Equivalent number:
|
-
|
|
Timing:
|
2028-06 (Medium priority)
|
|
Liaison:
|
IEC TC8, ISO/IEC JTC 1 SC39
|
|
Supporting members:
|
China Unicom, China Telecom, China Mobile, ZTE, CAICT,State Grid Corporation of China, Huawei Technologies
|
|
Summary:
|
This Recommendation specifies general requirements for Hybrid Energy Storage Systems (HESS) deployed in AI computing centres (AIDCs). It addresses the unique challenges posed by GPU-driven workloads, including millisecond-level power transients, high-frequency micro-cycling, and the competing demands of transient response, power fluctuation smoothing, and long-duration backup.
The Recommendation establishes requirements for HESS scheduling in AIDC, covering: power allocation and capacity dispatch based on load power spectral density; coordination with AI workload schedulers for pre-charging and carbon-aware operation; grid interaction management including harmonic compensation, islanding detection, seamless transition, and fault ride-through; state-of-charge and lifecycle management with active micro-cycle suppression; frequency decomposition for multi-timescale power allocation; virtual inertia and damping control using the high-power layer; dynamic backup capacity reservation; and PCS coordination for stable multi-layer operation.
|
|