Work item: K.45 (2019) Amd.1 (ex K.45 Amd.1)
Subject/title: Amendment 1 to Recommendation ITU-T K.45: Resistibility of telecommunication equipment installed in the access and trunk networks to overvoltages and overcurrents
Status: Approved on 2020-06-29 
Approval process: AAP
Type of work item: Recommendation
Version: -
Equivalent number: -
Timing: -
Liaison: -
Supporting members: -
Summary: Amendment 1 to Recommendation ITU-T K.45 refers to Annex A. Annex A applies to special environments, one factor being that the primary protection has a poor earth connection that does not meet the requirements of Recommendation ITU-T K.66. This condition is simulated by increasing the STP earth resistance (R1) from zero to 100. People have missed this change, possibly because the test circuit diagram is in Recommendation ITU-T K.44. To alert readers of this a text note has been inserted in the Comments column.