Page 985 - 5G Basics - Core Network Aspects
P. 985

Transport aspects                                              2


            NOTE: If RMC frames are received with no errors, the FRA-R is expected to arrive in less than 6ms (this takes into
            account the response time and some margin for transmission time).

            13.3.1.1.1  Parameters controlling the FRA procedure
            The list of DPU-MIB parameters controlling the FRA procedure is presented in Table 13-9. These parameters
            are used in the FRA triggering criteria defined in clause 13.3.1.1.1.5.
            Each of the four FRA triggering parameters can have different values for the FTU-O (upstream) and the
            FTU-R (downstream).
            •       FTU-O (upstream): Configured through the DPU-MIB.
            •       FTU-R (downstream): Configured through the DPU-MIB and communicated to the FTU-R during
                    initialization (in O-MSG 1 message).


                                   Table 13-9 – Parameters controlling the FRA procedures

                Parameter                                        Definition
             FRA-TIME         FRA-TIME determines the duration of the FRA time window used in the standard FRA
                              triggering criteria.
             FRA-NTONES       FRA-NTONES determines the minimum percentage of subcarriers with bi>0 that are to be
                              detected as degraded ones over the time window equal to FRA–TIME in order to arm the first
                              FRA triggering criterion.
             FRA-RTX-UC       FRA-RTX-UC determines the minimum number of rtx–uc anomalies received throughout a time
                              window equal to FRA–TIMEds in order to arm the second FRA triggering criterion.
             FRA-VENDISC      Determines whether vendor-discretionary FRA triggering criteria may be used.
            The  control  parameters  fra-ntones  (see  clause  13.3.1.1.1.2),  fra-rtx-uc  (see  clause  13.3.1.1.1.3),  and
            fra-time (see clause 13.3.1.1.1.1) are derived from the DPU-MIB parameters FRA-NTONES, FRA-RTX-UC, and
            FRA-TIME.  The  value  zero  for  FRA-TIME  in  the  DPU-MIB  indicates  that  vendor  discretionary  values  for
            fra-ntones,  fra-rtx-uc,  and  fra-time  may  be  used  instead  of  the  values  configured  in  the  DPU-MIB  for
            FRA-NTONES, FRA-RTX-UC, and FRA-TIME, respectively.

            The control parameter fra-vendisc is equal to the DPU-MIB parameter FRA-VENDISC. The value ONE for
            FRA-VENDISC indicates that vendor discretionary FRA triggering criteria may be used. The value ZERO for
            FRA-VENDISC indicates that vendor discretionary FRA triggering criteria shall not be used.

            13.3.1.1.1.1    FRA time window (fra-time)
            The fra-time is the duration of the time window used in the standard FRA triggering criteria (see clause
            13.3.1.1.1.5). This time window shall be applied to contiguous non-overlapping time steps. The start time of
            this window is vendor discretionary. The valid range of non-zero values is from one logical frame length to
            one superframe length in steps of one logical frame length. The special valid value zero shall be used to
            indicate  that  both  monitoring  of  the  percentage  of  degraded  subcarriers  (see  clause 13.3.1.1.1.2)  and
            monitoring of the number of rtx-uc anomalies (see clause 13.3.1.1.1.3) are disabled.

            The  fra-time  defined  for  the  downstream  and  upstream  are  denoted  as  fra-time-ds  and  fra-time-us,
            respectively.

            13.3.1.1.1.2    Minimum percentage of degraded tones (fra-ntones)

            The  fra-ntones  is  the  minimum  percentage  of  loaded  subcarriers  (i.e.,  subcarriers  with  bi>0)  that  are
            detected as degraded throughout a time window equal to fra-time in order to arm the first FRA triggering
            criteria (see clause 13.3.1.1.1.5).
            A degraded subcarrier is a subcarrier that has been identified as needing a reduction in active bit loading
            because, with its current active bit loading, it is expected to contribute substantially to the decrease of
            SNRM. The valid range of non-zero values is from one to 100 in step of one. The valid value zero shall be



                                                                                                         975
   980   981   982   983   984   985   986   987   988   989   990