Page 798 - 5G Basics - Core Network Aspects
P. 798

2                                                 Transport aspects


            10.3.2.5   Identification of the VFRB

            10.3.2.5.1  Frequency identification control parameters
            Frequency identification allows to reduce the size of the VFRB and to fit the corresponding eoc or SOC
            message into the desired number of superframe periods (usually one superframe) by reducing the number
            of reported VF samples. Frequency identification is defined by two parameters:
            •       the frequency sub-sampling factor (F_sub);
            •       the frequency shift step (s).

            Frequency identification is enabled by setting s ≠ 0.
            With sub-sampling rate of F_sub, VF samples for a particular element X of the probe sequence are reported
            only for subcarriers of the given vectored band with indices:
                                           i = imin + (s×(n-1))MOD(F_sub) + j×F_sub

            where:
                            imin  is the lowest index of the vectored band;
                            j =  0, 1, 2…
            n is a count of probe sequence cycles covered by the reports; for the first report, n=1.
            For example, if F_sub = 4, at the first probe sequence cycle (n=1) all subcarriers with indices imin+j×4, j = 0, 1,
            2… will be reported until the upper index of the vectored band. At the second probe sequence cycle (n=2),
            the starting subcarrier index is increased by s. If s = 2, all subcarriers with indices imin+2+j×4 will be reported
            at the second probe sequence cycle. These two reports will provide one set of VF samples equivalent to a
            single report with F_sub = 2 (no more reports are required because in the next probe sequence cycle (n=3)
            the subcarriers with indices imin+j×4, j = 0, 1, 2… will be reported again).
            The valid values of frequency identification control parameters are presented in Table 10-11.


                           Table 10-11 – Valid values of frequency identification control parameters

               Parameter             Valid values for VCE              Mandatory values for FTU-R to support

             F_sub         As per Table 10-10                     All valid values.
             s             1, 2, 3, 4 provided that s < F_sub (Note)   All valid values.
             NOTE – s = 0 is a special value indicating that frequency identification is disabled.
            For frequency identification reporting:
            –       To start vectoring feedback reporting, the value of parameter q shall be set to 1.

            –       To stop vectoring feedback reporting, the value of parameter q shall be set to 0.
            10.3.2.5.2  Time identification control parameters

            On each of the sync symbols indicated by the FTU-O by the associated superframe count, the FTU-R shall
            transmit  a  single  VFRB.  In  each  VFRB,  the  FTU-R  shall  also  include  the  superframe  count  (as  defined  in
            clause 12.3.3.2.6) as identification of the downstream sync symbol the VFRB corresponds to. The FTU-O
            shall indicate such superframe counts using the following time identification control parameters:
            •       the VFRB update period (q);
            •       the VFRB shift period (z).
            Time identification is enabled by setting s = 0.

            The  FTU-R  shall  send  the  first  VFRB  on  the  first  sync  symbol  following  the  reception  of  the  request  to
            update  the  VFRB  control  parameters.  Then  it  shall  send  a  VFRB  on  every  q-th  subsequent  sync  symbol
            position z-1 times. After z VFRBs are sent (which takes q×z superframes), the next VFRB shall be reported




            788
   793   794   795   796   797   798   799   800   801   802   803