ITU

Committed to connecting the world

ITU-T work programme

[2009-2012] : [SG5] : [Q5/5]

[Declared patent(s)]  - [Publication]

Work item: K.56
Status: Approved on 2010-01-13 [Issued from previous study period]
Approval process: AAP
Type of work item: Recommendation
Version: Rev.
Provisional name: -
Equivalent number: -
Timing: -
Liaison: ETSI ERM
Subject/title: Protection of radio base stations against lightning discharges
Summary: This Recommendation presents the techniques applied to a telecommunication radio base station in order to protect it against lightning discharges. The need of protection is obtained from the methodology contained in [IEC 62305-2], which is used to determine the relevant lightning protection level (LPL) for the installation. The protection techniques for the external area cover the lightning protection system (LPS), bonding procedures, earthing, and the installation of surge protective devices (SPD) at the power meter station. The protection techniques for the equipment building cover the feeder and lighting cables, the electric power conductors, the telecommunication cabling, and the earthing / bonding procedures applied to cable trays and equipment frames. This Recommendation also provides guide-lines in order to achieve adequate protection of the telecommunication equipment based on the coordination between equipment resistibility, SPD protection level, and installation characteristics.
Comment: -
Base text(s):
Contact(s):
ITU-T A.5 reference(s):
Generate A.5 drat TD
-
[Submit new A.5 reference ] 
First registration in the WP: 2009-10-16 12:02:13
Last update: 2010-02-12 17:36:54